|
Primary Changes in the IRC
Chapter #3 Building Planning
| TOPIC |
VOL VII |
IRC (NEW) |
|
Emergency Escape & Rescue Openings |
|
New section R310.2 was added to include window wells |
|
Guards |
Was called Guardrails under Old section 315 "Handrails & Guardrails" |
New Section R316.1 Guards Required., changed minimum height of guards to 36" and deleted
Maximum height requirement. |
|
Smoke Alarms |
Section 316 Smoke Detectors (installed in accordance w/the Electrical Code |
Section R317 Smoke Alarms, required
In each room for sleeping purposes, outside each sleeping area on wall or
Ceiling, and each story within the dwelling unit.
R317.1.1 Smoke Alarm Requirements for Repairs & Additions
R317.2 explains power source requirements. |
|
Site Address |
|
R325 Site Address…..requires address nos. visible from street. |
|
Accessibility |
|
Section R326 shall comply with the North Carolina Accessibility Code. |
|
Flood Resistant Construction |
|
New Section R327 Flood Resistant Construction….R327.1 through R327.3.5 denotes requirements for structures in floodways |
Chapter # 4
Foundations
|
Topic |
Old Code (CABO) |
New Code (IRC) |
|
Foundation |
R401 |
Section R401.1: added exception #2, concerning foundations in areas prone to flooding |
|
Geotechnical evaluation |
R401.4.1 |
R401.4.1…revised table…added notes a & b, under Class Of Materials added, and foliated rock, added silt and sandy silt, and abbreviations for soil types |
|
Wood treatment |
R402.1.2 |
R402.1.2 section was reworded |
|
Concrete |
R402.2 |
R402.2, all materials used to produce concrete shall comply with ACI318 and cement complying with ASTMC1157 is permitted |
|
Footings |
R403 |
R403.1 section was reworded, basically the same content |
|
Footings |
R403.1.1 (slope) |
R403.1.5, new section number, same content, sections R403.1.2 through R403.1.4 do not apply in Wake County |
|
Footings |
|
R403.1.1, minimum size footings (new section) |
|
Foundation anchorage |
Figure 403.1a, note # 5 omitted |
R403.1.6 |
|
Footings on or adjacent to slopes |
Section did exist |
R403.1.7 deleted |
|
Insulated footings |
R403.3 |
Section deleted |
|
Design required |
R404.1.2 |
Section R404.1.3 design required when the foundation wall is subject to hydrostatic pressure and walls supporting more than 48" of unbalanced fill without permanent lateral support at the top and bottom. |
|
Foundation walls, seismic requirements |
|
R404.1.4 does not apply in Wake County. |
|
Foundation wall thickness based on wall support |
|
R404.1.5 |
|
Pier and curtain wall |
R604.5.2 |
R404.1.5.1 section was relocated |
|
Piers |
R604.5 |
R404.1.5.2 section was relocated |
|
Height above finished grade |
R404.1.3, foundation wall shall extend 8" above grade, brick veneer: 4" above grade |
R404.1.6, foundation wall shall extend 4" above grade, brick veneer 6" above grade |
|
Backfill placement |
R404.1.3.1, exception: bracing not required for unbalanced fill of less than 3'-0" |
R404.1.7, exception: changed to 4'-0" |
|
Rubble stone masonry |
R604.2.2 |
R404.1.8, added maximum 8'-0" of unbalanced fill and maximum soil pressure of 30psf |
|
Wood foundation walls |
R404.3 |
R404.2 |
|
Wood grade |
R404.3.1 |
R404.2.1 reworded to be more specific |
|
Fastening |
|
R404.2.6 new section |
|
Wood sill plates |
|
R404.3, new section, minimum sill plate 2"x4" |
|
Insulating concrete form foundation walls (ICF) |
|
R404.4 new section, if walls are designed in accordance with ACI318 or this section, seal of an architect or engineer is not required |
|
Foundation drainage |
|
R405.1, exception #2 was added, system is not required when the interior grade is less than 12" below the exterior grade |
|
Concrete and masonry foundation waterproofing |
|
R406.2, Exception was added |
|
Final grade |
R406.3.5 |
Omitted |
|
Foundation insulation |
R407 |
Omitted |
|
Columns |
R408 |
R407.3, added exception for seismic design categories A,B,C (Wake Co. is in category B) |
|
Crawl space ventilation |
R409.1 |
R408.1, added "one such ventilating opening shall be within 3' of each corner |
|
|
R409.1 |
R408.2, exception #2 revised: one ventilation opening does not have to be within 3' of each corner and operable vents are not permitted |
|
|
R409.1, exception # 3 was omitted in the IRC |
R408.2, exception # 5 is a new item where the ventilation is not required when the ground is covered with an approved vapor barrier, the space is supplied with conditioned air and the walls are insulated |
|
Finished grade |
R409.4, ground water table cannot rise within 6" of the finished floor at the building perimeter |
408.5 revised, ground water table cannot rise within 6" of the finished grade of the under-floor space at the building perimeter |
|
Flood resistance |
|
R408.6 new section |
|
|
|
|
|
Chapter # 5
Floors
|
TOPIC |
VOL VII (old) |
IRC (new) |
|
Prefabricated wood I-joist |
|
R502.2 Prefabricated wood I-joists. Requirements shall be in accordance with ASTM D 5055. |
|
Decks |
501.3 Exterior Decks …shall be in accordance with Appendix A. |
R502.2.1 Decks..refer to table R301.4 for live load …also decks shall be permitted to be constructed in accordance with Appendix M. |
|
Allowable Joist Spans |
502.3.1 Allowable joist spans refer to tables 502.3.1a through 502.3.1b |
R502.3 Allowable joist spans. Refer to new tables R502.3.1(1) And R502.3.1(2). Note: these tables have been simplified & are much easier to read (also note sleeping areas & living areas. |
Chapter # 6
Wall Construction
| Topic |
Old code (CABO) |
New (IRC) |
|
Wood wall framing |
|
R602.2.2, new section, End joint lumber |
|
Design and construction |
R602.3, section was called Exterior Walls |
R602.3, new section is called Design and Construction, added "or in accordance with AF&PA's NDS |
|
Stud spacing |
R602.3.1 |
R602.3.1, added bearing studs greater than 10 feet, see table R602.3.1 |
|
Top plate |
R602.3.2, end joints shall be offset at least 48". |
R602.3.2, end joints shall be offset at least 24". |
|
Bottom (sole) plate |
|
R602.3.4 studs shall have full bearing on a nominal 2 by or larger plate. |
|
Drilling and notching of studs |
R602.5 |
R602.6
Added exceptions # 2,3 |
|
Drilling and notching of the top plate |
R602.5.1 used 24 gauge angle to repair cut top plate |
R602.6.1 revised, must use 16 gauge angle to repair cut top plate. Added an exception, use of wood structural sheathing |
|
Fastener schedule for structural members |
Table 602.3a
Double top plates, minimum 48" offset of end joints, face nailed in lapped area, nail with 4-10d |
Table 602.3 (1)
Double top plates, minimum 48" offset of end joints, face nailed in lapped area, nail with 8-16d
Added: blocking between joists or rafters to top plate, toe nail with 3-8d
Added: rim joist to top plate, toe nail with 8d, 6"oc
Added: other wall sheathing, ½" regular cellulosic fiberboard sheathing, ½" structural cellulosic fiberboard sheathing
** subnotes were changed from a number system to a letter system
revised subnote f from 90 mph to 110 mph
revised subnote g from 80 mph to 100 mph
Added subnote I |
|
Alternate attachments |
Table 602.3a (1) |
Table 602.3 (2)
Changed all sub notes from numbers to letters. Subnote c revised: Nails or staples shall be spaced at no more than 12" on center at intermediate supports for floors. Added subnote f.
Wood structural panels subfloor, etc., 5/16"; 3/8" ; 15/32" ; ½" added staple 16 ga. 1 ¾"
23/32" and ¾" added staple 16 ga. 2"
Floor underlayment, etc.
Plywood
¼" and 5/16" added staple 18 ga. 7/8", 3/16" crown width
19/32", 5/8", 23/32", ¾" added staple 16 ga. 1 1/4" |
|
Exterior bearing walls
First floor of 3 story
Exterior non bearing walls |
Table 602.3e
Wind zone 70 mph
Wind zone 80 mph
Table 602.3e
Wind zone 70 mph
Wind zone 80 mph |
Table 602.3 (6)
Wind zone 90 mph
Wind zone 100 mph
Table 602.3 (6)
Wind zone 90 mph
Wind zone 100 mph |
|
Wood structural panel box headers |
Figure 602.6.2
Table 602.6.2 |
Figure 602.7.2
Added sub note # f: galvanized nails shall be hot dipped or tumbled.
Table 602.7.2 |
|
Maximum allowable length of wood wall studs exposed to wind speeds of 100 mph or less in seismic design
Categories A, B, C, D |
|
New table 602.3.1 |
|
Nonbearing walls |
R602.6.4 |
R602.7.2 (new section number) |
|
Fire blocking |
R602.7 |
R602.8
Basically the same text as the old CABO code but it is more defined and areas where fire blocking are required are more specific. |
|
Cripple walls |
R602.8 |
R602.9
Added: cripple walls with a stud height of less than 14 inches shall be sheathed on at least one side with a wood structural structural panel that is fastened to both the top and bottom plates in accordance with table R602.3 (1), or the cripple walls shall be construction of solid blocking. Cripple walls shall be supported on continuous foundations. |
|
Wall bracing |
R602.9 |
R602.10
Section was completely revised. There is too much material to list here, must study all the new requirements directly from the code. |
|
Steel wall framing |
R603 Metal |
R603 new section |
|
Wood structural panels |
R610 |
R604 |
|
Particle board |
R611 |
R605 |
|
General masonry construction |
R604 |
R606 |
|
Professional registration not required |
R604.1.1 |
R606.1.1, revised to read : "when the empirical design provisions of ACI 530/ASCE 5/TMS 402 Chapter 5"…. |
|
Used brick |
R604.1.2 |
R606.1.2, added an exception for interior non bearing conditions |
|
Parapet walls |
R604.2.4 |
R606.2.4, added: Masonry parapet walls in areas subject to wind loads of 30 pounds per square foot or located in seismic design category D1 or D2 shall be reinforced in accordance with section R606.11. |
|
Roof structures |
R604.8.2.1, "Anchors shall be embedded at least 16" into masonry…" |
R606.8.2.1, revised: "Anchors shall be embedded at least 15" into masonry…" |
|
Spacing of lateral support for masonry walls |
Table604.8 |
Table R606.8, omitted subnote # 3: For 100mph or greater see chapter 40 for h/t ratios |
|
Anchorage requirements for masonry walls located in Seismic Design Category A,B,C and where wind loads are less than 30psf |
Figure 604.10a
Rafter/ceiling joists anchor embedded 4" min.
Joists parallel to wall: ½" bolts at 6ft.o/c embedded at 4 " min. |
Figure R606.10 (1)
Rafter/ceiling joists anchor embedded 15" min.
Joists parallel to wall: ½" bolts at 8ft.o/c embedded at 4 " min.
Ledger bolt size and spacing table, decreased joist span from 15'-30' to 15'-20' |
|
Unit masonry |
Section R605 |
Section R607
607.1 Mortar: defines minimum mortar specifications
607.1.1 Foundation Walls and 607.1.2 Masonry in Seismic Design Categories A, B (Wake Co.) and C.
These sections define the minimum mortar specifications for each application.
607.1.3 does not apply in Wake Co. |
|
Bed and head joints |
R605.1.1.1 |
R607.2.1.1: deleted collar joints
Added Exception:
"For the purposes of leveling, the thickness of the bed joint of the starting course placed over the foundation shall not be less than ¼" and not more than 1 ½".
R607.2.1 Bed and Head Joints: "Unless otherwise required or indicated on the project drawings, head and bed joints shall be 3/8" thick. |
|
Mortar Proportions |
Table 607.1.1a |
Table R607.1
Added mortar cement |
|
Multiple Wythe Masonry |
R606 |
R608
No changes |
|
Grouted Masonry |
R607.1.1 |
R609.1.1. omitted "Only type M or Type S mortar mix consisting of Portland cement, hydrated lime, and sand in accordance with ASTM C 270…" |
|
Glass Unit Masonry |
Section did not exist |
R610, new section |
|
Insulating Concrete Form Wall Construction |
Section did not exist |
R611, new section |
|
Conventionally Formed Concrete Wall Construction |
Section did not exist |
R612, new section |
|
Exterior Windows and Glass doors |
R608, 609, 613 |
R613, combined the 3 CABO sections into this one new section. |
Chapter # 7 Wall Covering
| Topic |
Old Code (CABO) |
New Code (IRC) |
|
Thickness of Plaster (interior) |
Table 702.1a |
Table R702.1(1), added gypsum sheathing, changed all subnotes from numbers to letters. |
| |
|
Table R702.1(1), added subnote g |
|
Minimum Thickness and Application of Gypsum Board |
Table 702.3.4 |
Table 702.3.5, application is specific to wall or ceiling. The subnotes are rewritten. |
|
Support |
R702.2.1 |
R702.2.1, added…"16" on center for 3/8" thick….plain gypsum lathe. Added…."with end joints in adjacent courses staggered by at least one framing space." |
|
Application |
R702.3.4 |
R702.3.5 |
|
Fastening |
R702.3.5 |
R702.3.6 |
|
Insulating Concrete Form Walls |
|
R702.3.4, new section |
|
Bathtub and shower spaces |
R702.4 |
R307.2 |
|
Ceramic Tile |
R702.4.1 |
R702.4.2 GYPSUM BACKER…"shall conform to ASTM C 630 or C 1178."
"ceilings where framing spacing does not exceed 12 inches on center for ½" thick or 16 inches for 5/8 inch thick gypsum board." |
|
Other Finishes |
R702.5 |
R702.5.completely rewritten, see code book |
|
Bottom Course |
R702.6.3 |
R703.5.4 |
|
Plaster |
|
R703.6.2 new section |
|
Ceramic Tile |
R702.4.1 |
R702.4.1 General: Ceramic tile surfaces shall be installed in accordance with ANSI A108.4, A108.5, A108.6, A108.11, A118.1, A118.3, A136.1 and A137.1. |
| |
R702.4.1 |
R702.4.2 Gypsum Backer. "….shall conform to ASTM C630 or C1178." "…12 inches on center for 5/8 inch thick or 16 inches on center for ½ inch thick gypsum board." |
|
Other finishes |
R702.5 |
R702.5: completely rewritten. |
|
Exterior Covering |
R703.1 General |
R703.1 General: added "The exterior wall envelope shall include flashing as described in Section 703.8. The exterior wall envelope shall be designed and constructed in such a manner as to prevent the accumulation of water within the wall assembly by providing a water resistive barrier behind the exterior veneer as required by Section R703.2." |
|
Weather-resistant sheathing paper |
R703.2 |
R703.2…added: "and complying with ASTM D 226" |
|
Exceptions |
R703.2.1 Felt or material
No.5. over water repellant sheathing materials |
R703.2, Exceptions, no.5 was deleted |
|
Panel Siding |
R703.3 |
R703.1…added: "or shall be shiplapped…..and occur over solid blocking, wood or wood structural panel sheathing." |
|
Plaster |
|
R703.6.2 new section |
|
Panel siding |
R703.3.1 |
R703.3 added "…and occur over solid blocking, wood or wood structural panel sheathing." |
|
Bottom courses (exterior) |
|
R703.5.4: shall be doubled |
|
Weather-resistant siding attachment and minimum thickness |
Table 703.4 |
Table 703.4: added subnotes o,p,q,r. |
|
Stone and masonry veneer |
R703.7 |
R703.7, revised for Wake Co., max. ht. of 30 feet above the noncombustible foundation, with an additional 8 feet permitted for gable ends. |
|
Anchorage |
R703.7.2 |
R703.7.4, rewritten (see IRC) |
|
Air space |
Figure 703.7(b) |
R703.7.4.2, min.1", max. 4.5" |
|
Mortar or grout fill |
R703.7.2.3 |
R703.7.4.3, rewritten (see IRC) |
|
Flashing |
R703.7.3 |
R703.7.5, rewritten (see IRC) |
|
Flashing |
R703.8 |
R703.8, rewritten (see IRC) |
|
Exterior insulation finish systems |
Did not exist |
R703.9, new section (see IRC) |
|
Masonry veneered wall detail |
Figure 703.7(b) |
Figure R703.7, R703.7.1 |
Chapter # 8
Roof-ceiling Construction
| Topic |
CABO |
IRC |
| Framing of openings |
R802.9 |
R802.9, added "Approved hangers shall be used for the header to trimmer connections when the header span exceeds 6 feet. Tail members over 12 feet long shall be supported at the header by framing anchors or on ledger strips not less than 2 inches b 2 inches."
Exception: all dormers shall have double headers and double rafters. |
| Wood trusses |
R802.11 |
R802.10: section has been completely rewritten (see IRC). |
| Roof tie down |
R802.12 |
R802.11: section has been rewritten, table R802.11 replaces table 802.12. |
|
Wood structural panel sheathing |
R803.2 (plywood sheathing)
R803.2.1.3 (wood structural panels)
R803.3 (particle board) |
R803.2: combined all of the CABO sections into one section. |
| Allowable loads for particleboard roof sheathing |
Table 803.3.2 |
Table was deleted |
|
Steel roof framing |
R804 |
R804: completely new section must see new IRC. |
|
Attic access |
R807.1 |
R807.1: added, "In buildings with combustible ceiling or roof construction, an attic access opening shall be provided to attic areas that exceed 30 sq. ft. and have a vertical height of 30 inches or greater. The roughed framed opening shall not be less than 22 inches by 30 inches and shall be located in a hallway or other readily accessible location. A 30 inch minimum unobstructed headroom in the attic space shall be provided at some point above the access opening." |
|
Allowable spans for ceiling joists |
|
Tables have been redesigned to reflect spans and live loads to the different species of lumber. |
|
Insulation clearance |
|
R808: new section, "combustible insulation shall be separated a minimum of 3 inches from recessed lighting fixtures, fan motors and other heat producing devices." |
Chapter # 9 Roof Assemblies
|
Topic |
CABO |
IRC |
|
Roof Classification (Roofing covering materials) |
R901.3 |
R902.1, revised….."set forth in Sections R904 and R905. Class A,B,C roofing… with UL790 or ASTM E 108." |
|
Roof Classification (Wood shingles and shakes) |
|
R902.2: new section, shall conform to ASTM E 108 and ASTM D 2898 |
|
Fire retardant treated shingles and shakes |
|
R902.2.1: new section, shall conform to AWPA C1 and R902.2 |
|
Weather protection |
|
R903, new section, includes sections on flashing, coping, roof drainage, overflow drains and scuppers. |
|
Materials |
|
R904, new section, includes sections on compatibility of materials, material specifications and physical characteristics, product identification. |
|
Requirements for roof coverings |
R903 asphalt shingles |
R905.2.3 (underlayment) shall conform with ASTMM D226, Type I or ASTM D 4869, Type I. (see IRC for additional information). |
|
|
|
R905.2.4, asphalt shingles shall comply with ASTM D 225 or D 3462. |
|
|
|
R905.2.5, fasteners shall comply with ASTM F 1667 |
|
|
|
R905.2.7.1 (ice protection), new section. |
|
Flashing |
R903.5 |
R905.2.8: section was completely rewritten with much more information, must see IRC. |
|
Clay and concrete tile |
R906 |
R905.3, deck slope, shall be installed on roof slopes of 2.5:12 or greater. Slopes from 2.5:12 to 4:12, double underlayment application is required in accordance with section R905.3.3. |
|
|
|
R905.3.3, underlayment, shall conform with ASTM D 226, Type II, ASTM D 2626, Type I, or ASTM D 249, mineral surfaced roll roofing. |
|
|
|
Table R905.3.5: new table,
Transverse Breaking Strength of Concrete Roof Tile |
|
|
|
Table R905.3.7: new table,
Clay and Concrete Tile Attachment |
|
Metal Roof Shingles |
R905 |
R905.4 |
|
|
R905.4 underlayment |
R905.4.3 underlayment shall comply with ASTM D 226, Type I |
|
|
R905.2 Materials |
R905.4.4 Materials Standards, completely rewritten see IRC |
|
|
|
R905.4.6 Flashing, new section, see IRC |
|
Mineral Surfaced Roll Roofing |
|
R905.5.2.Deck Slope: shall not be installed on roof slopes below one unit vertical in 12 units horizontal. |
|
|
|
R905.5.3 Underlayment shall conform to ASTM D 226, Type I. |
|
|
|
R905.5.4 Material Standards shall conform to ASTM D 224, D 249, D371, D 3909. |
|
|
|
R905.5.5 Application per this chapter and manufacturer's installation instructions. |
|
Slate and Slate Type Shingles |
R904 |
R905.6 comply with the provisions of this chapter. |
|
|
|
R905.6.2 Deck Slope: shall not be installed on roof slopes of four unit vertical in 12 units horizontal or greater. |
|
|
R904.3 |
R905.6.3 Underlayment shall conform to ASTM D 226, Type II. |
|
|
|
R905.6.5 Application: minimum headlap per TableR905.6.5, secured to roof with 2 fasteners per slate and manufacturer's installation instructions. |
|
|
R904.4 |
R905.6.6 Flashing, rewritten, see IRC. |
|
Wood Shingles |
R908 |
R905.7 |
|
|
|
R905.7.2 Deck Slope: 3 units vertical in 12 units horizontal. |
|
|
|
R905.7.3 Underlayment shall comply with ASTM D 226, Type I. |
|
|
R908.2 |
R905.7.4 Material Standards shall comply with Table R905.7.4. |
|
|
R908.3 |
R905.7.5 Application: shall be installed per this chapter and the manufacturer's installation instructions. Weather exposure for woos shingles shall not exceed those set in Table R905.7.5, see IRC for additional information. |
|
Valley Flashing |
R908.3.2 |
R905.7.6: "flashing shall not be less than 26 ga……and 7 inches from the centerline each way for slopes of 12 units vertical in 12 units horizontal and greater." |
|